AWG Wire Gauge Calculator

Enter an AWG number (use 0 for 1/0, -1 for 2/0, -2 for 3/0 and -3 for 4/0) to get the exact diameter, area and resistance at 20 C. For learning and design checks, not safety certification.

Updated

Embed this calculator

Paste this code into your page. The calculator runs inside the frame and links back to the full version.

Keep the credit link in place. Do not resell the calculator.

Formula

  • Diameter: d (mm) = 0.127 × 92^((36 − n) ÷ 39), with n = -3, -2, -1 for 4/0, 3/0, 2/0
  • Area: A = π ÷ 4 × d²
  • Resistance per metre: R = ρ ÷ A, with copper ρ = 1.7241e-8 ohm m at 20 C
  • Per 1000 ft: multiply the per-metre value by 304.8
  • Current guide: A × 6 A/mm², general guidance only

Worked example

AWG 10: d = 0.127 × 92^(26 ÷ 39) = 2.588 mm (0.1019 in). Area is π ÷ 4 × 2.588² = 5.261 mm². Resistance is 1.7241e-8 ÷ 5.261e-6 = 0.003277 ohm/m, which is 0.9989 ohm per 1000 ft. The rough current guide is 5.261 × 6 = 31.6 A; treat it as guidance, not a rating.

Frequently asked questions

What is the AWG diameter formula?

d = 0.127 mm x 92^((36 - n)/39), where n is the gauge. For AWG 10 that is 0.127 x 92^(26/39) = 2.588 mm.

How is wire resistance worked out?

R = resistivity x length / area. Annealed copper at 20 C is 1.7241e-8 ohm m, so AWG 10 (5.261 mm2) is 0.003277 ohm per metre, or 0.9989 ohm per 1000 ft.

Does a smaller AWG number mean thicker wire?

Yes. Every 6 gauge steps roughly halves the diameter, and every 3 steps roughly halves the area. AWG 0 is 8.25 mm across, while AWG 36 is 0.127 mm.

How many amps can a wire carry?

The current guide here is general guidance only (about 6 A per mm2, so 31.6 A for AWG 10). Safe current depends on insulation, temperature, bundling and wiring rules, so use a code table; this is for learning and design checks, not safety certification.